WiFi electricity meter with protection and control functions, EM-129 by Novatek-Electro

2800₴ (около $105)
Go to store
This device is hard to classify as a "household" product, although of course it can certainly be used that way. Its main applications are small businesses, office buildings, rental properties, and so on.
Even so, I found it interesting in its own right, and I’m planning to use one at home. But it’s best to read the full review for all the details.


Before describing the device and reviewing it, I think a brief clarification is in order to avoid any confusion.
The title calls it an electricity meter, but this meter is intended for non-commercial use. In other words, you can’t use it in place of a standard meter and have it sealed. It has somewhat different functions, and at least one of them is incompatible with that kind of use.
You might reasonably ask: what’s the point of a meter like this, then? I’ll answer that and other questions in the review. And if I miss anything, you can always ask in the comments—especially since I can forward any particularly tricky questions to the manufacturer for clarification.

To make this easier to understand, let’s imagine a hypothetical situation: you inherit a large building from a distant relative, divide it into several units, renovate it, and decide to rent them out—some as offices, some as shops, and perhaps one as a warehouse. Everyone needs electricity, and you’d like not only to track consumption but also to have some additional features.
I’ll use this example to explain the features of the EM-129.

The device comes in the same branded packaging as before. Without the sticker, you could probably mistake it for the previous model.


The contents are the same: the module and the manual.


In this case, though, it’s probably not just a manual but a whole tome, with a complete description of how it works, how to configure it, and how to use it.
One interesting detail: the website lists a 5-year warranty, while the passport and PDF file say 10 years. As I understand it, the printed passport takes precedence.


Before taking a closer look, here’s a brief description from the passport, along with the technical specifications.

Product purpose
The EM-129 is a Wi-Fi-connected microprocessor device designed for non-commercial electricity metering.
The EM-129 can switch electrical equipment (refrigerators, air conditioners, washing machines, TVs, video and audio equipment, etc.) on and off according to a schedule or manually, while also protecting it against various faults involving voltage, frequency, and power overloads.
The EM-129 stores a log of its operation and energy consumption data for the past month in its internal memory.
The EM-129 has overheat protection and disconnects the load if the temperature inside the enclosure exceeds 80 ºC (for example, due to the load current exceeding its rated value, poor contact caused by loose terminal screws, etc.).
The EM-129 has one control button (for entering Wi-Fi setup mode or manually controlling the load) and a two-color indicator (to show faults, load status, and Wi-Fi connection status).
When connected to the «my.overvis.com» service, the EM-129 can be controlled from anywhere in the world with an internet connection.
You can save electricity and money by using the EM-129 to control heating or ventilation equipment according to a preset schedule.

Main features:
Measures the electricity consumed by the load;
Measures mains voltage and frequency;
Measures the current drawn by the load;
Measures the power consumed by the load;
Protects the load against mains voltage faults;
Protects the load against excessive current draw;
Protects the load against excessive power consumption;
Protects internal components against overheating;
Real-time clock with up to 5 days of backup (when power is off);
Automatically synchronizes the time with a network time server (NTP);
Automatically controls the load according to a user-defined schedule;
Limits the load’s operating time;
Manual load control from the front panel;
Disables manual control after a specified period.

The technical specifications are largely the same as those of the RN-263t voltage relay, with control and monitoring capabilities added. More on that later.

I later discovered that the electronic and printed versions of the manual differ in their stated technical specifications:
1. Startup time after power is applied: 0.4s 1.5s
2. Measured voltage: 50-450V 100-350V.
3. Power measurement range: 15-30000W 300-30000W.
4. Overvoltage category: II III


The module comes with a strip bearing self-adhesive stickers with the device's MAC address and unique number for remote control.


It's 2 modules wide, or 35 mm, and has the same enclosure as the RN-263t.


The input and output are marked on the enclosure. Only the phase conductor is switched, so if needed, you can use a three-wire connection with a smaller-gauge neutral conductor.
The wiring diagram is printed on the enclosure, and the rail-mounting clip is spring-loaded. The manufacturer recommends connecting the device to the mains through a circuit breaker with a B trip curve and a maximum current rating of 63 A.


The front panel, however, is completely different from the RN-263t. That model had a voltage display, operating-mode LEDs and trimmer resistors; this one is as minimalist as it gets, with just one button and a two-color LED. In normal operation, it either blinks or glows blue (depending on whether it's connected),


But there are actually more indicator patterns, controlled by the button. There are essentially three modes:
1. Manually switch the relay on/off
2. Start Wi-Fi setup
3. Reset all settings to factory defaults


Switch it on and the LED starts blinking. If Wi-Fi is configured, it glows steadily once connected. Power consumption is about 1–1.2 W.

Indicator patterns
Status indicators:
· Blue (blinking) – connecting to a Wi-Fi access point;
· Blue (steady) – load is on and connected to Wi-Fi;
· Blue (blinks once every 5 seconds) – load is off and connected to Wi-Fi;
· Red (blinking) – reclosing countdown in progress;
· Red (steady) – fault detected or the device is locked out due to a fault;
· Blue and red (blinking) – Wi-Fi setup mode is active;
· Purple – settings are being reset to factory defaults, firmware is being updated,
or the «Wi-Fi» control button has been pressed.


Before testing, I decided to take a look inside first. Fortunately, the device is very easy to disassemble.


1. A closer look at the terminals. They clamp wires with a cross-section of at least 2.5 mm² securely; the maximum specified is 16 mm².
2. The construction is the same as in the RN-263t: the boards are joined at a right angle, and the upper board is additionally secured by clips, which are themselves held in place by the sides of the upper enclosure. Simple, reliable and elegant.
3, 4. The neutral bus is implemented in the same way as in the voltage relay.


The internals are clearly different, though. The only part I recognize from the RN-263t is the current-measurement circuit based on a dual op-amp.
On the left is a voltage converter based on TPS5430, in the middle is an AMS1117 linear regulator, and on the right is an STD2NK90Z MOSFET rated for up to 900 V.
There's another inductor on the right, but it serves as an EMI filter and is slightly cracked. That may be my fault, though in any case it doesn't matter for this part.



A photo from another angle. I noticed later that the resistor values in the current-sense shunt circuit are different: these are 2 kΩ each instead of 1 kΩ. Just an observation.
The soldering quality is excellent. The boards are spotless, even where the soldering was clearly done by hand. The little flux spot next to one of the pads is mine; I desoldered a wire so it wouldn't get in the way of the photos.


Since the device has an RTC (real-time clock), it also needs a backup power source. In this case it's not a battery but a supercapacitor, which I think is actually better here: replacing a battery in a device like this would be inconvenient, and a supercapacitor lasts longer. According to the manufacturer, after charging for an hour the clock will keep running for 5 days. But even if power is lost, you won't have to set the time again, since NTP synchronization is supported)
The board also has a small tantalum capacitor and a 330 µF polymer capacitor. The latter isn't soldered in the most elegant way—in effect, it's hanging in midair—but having a capacitor like this should clearly help under harsh operating conditions.


The power relay is exactly the same as the one in the RN-263t—the NRL709BC—so I see no point in testing it. If you're interested in the test and conclusions, you can read my review of the voltage relay.
The relay is rated for currents up to 80 A, while the device manufacturer specifies a maximum current of 63 A.


The internal electronics' power supply has a varistor and an interference-suppression capacitor. The varistor gave me pause, though, since it's rated for 420 V. But don't confuse it with ordinary varistors: this is an Epcos S10K420 rated for 420 V RMS, whereas ordinary varistors are rated for the mains peak voltage.
Still, the device is specified for a maximum continuous voltage of 450 V, while the varistor is rated for 420 V.

The photo also shows a temperature sensor. Here it's glued to the relay's power contact, which seems more appropriate to me, since the relay can get hotter than the other components during operation.


The power supply system here is clearly more complex. In full, it looks like this:
1. The input voltage goes to a linear regulator that uses a MOSFET as its regulating element.
2. Next is the main DC-DC converter, based on an LNK306 (first photo).
3. The relay control circuit and two auxiliary regulators, based on the TPS5430 and AMS1117, are powered by the first regulator.

The capacitor after the LNK306 is a Hitano 220 µF, 25 V unit (second photo). Two more small capacitors from the same manufacturer are located near the relay contacts.
At the input, after the linear regulator, there are two 4.7 µF, 400 V capacitors connected in parallel through an inductor to reduce mains interference. Another capacitor, 220 µF, 25 V, is next to them (third photo).

Everything looks very good and fairly reliable to me, with one exception: the varistor is effectively connected in parallel with the input terminals, with no fuse in series. The only protection is a bypass trace on the board near the gap (fourth photo).

The problem is that varistors must not be installed without a fuse upstream, and a 63 A circuit breaker is no substitute for one. I don't yet know why the designers did it this way, but I can say that if the varistor fails short, the trace will vaporize before the incoming circuit breaker trips, and the process may come with special effects. This could happen if the input voltage rises above 420 V. The odds are close to zero, but still.


The top of the second board has an ESP8266 WiFi chip and 25Q16 memory. It's interesting that the manufacturer didn't use a standard WiFi module, but designed its own board, complete with a WiFi antenna.
This board also has programming interfaces for both the ESP and the control microcontroller, most likely for an ST-Link in this case.


I didn't desolder the board, since the underside only has an STM32F091CCT6 32-bit microcontroller, a memory chip, and a few passive components.


As last time, the manufacturer provided the device schematic at my request. The schematic for the microcontroller board wouldn't be very useful, so I didn't ask for it, but I was interested in the power board schematic.
Broadly speaking, it confirms everything I've written above, especially about the power supply system. It also shows that the current and voltage measurement circuits are the same as in the RN-263t. For example, input voltage is measured during both half-cycles, which, under certain conditions, can speed up the response to a fault.


Let's move on to the tests. I'll start a little differently—not with the usual measurements, but with a description of the controls.
As you've probably noticed, this device has no display of its own, apart from an LED, so all the information is available only through a remote connection.

The manual describes the connection procedure in detail, and I can say that it matches reality: follow the steps in the right order and everything works. Sure, someone might ask, “What's so special about that?” To which I'd reply: I once had some cheap security cameras that were also supposed to be easy to connect. Yeah, in theory :)

Anyway, back to the device. There are two ways to connect: directly to the device itself or through the Overvis cloud service. The manufacturer strongly recommends the second option, and having tried both, I completely agree.
Connection is through a web interface, not an app. That may be a drawback, but it also has an advantage: cross-platform compatibility, i.e. You can connect using either your Android smartphone or a regular PC, and you’ll probably see screenshots of both options in this review.

First, a direct connection. Its advantage is that you don’t need any routers, access points, etc. You can also “reach” the device at any time, as long as it’s powered on.

Press the button on the device and hold it for 5–6 seconds, then release it. The LED should start flashing red and blue.
The device then creates an access point named EM-129. Connect to it.
Launch a browser and go to http://em.com,. This opens the web interface, where the first thing you’ll be prompted to do is connect to your access point. For some reason, my router wasn’t visible, although the others showed up just fine.


You can select the “log in to the device without a password” mode to access the settings, but it’s still best to set a password later.
A window opens with information about power, voltage, current, and frequency, along with... a large round button. The button has a simple function: turning the voltage supply to the relay output on and off. Scroll down to see power consumption for the month, week, and day, as well as the total. Both active and apparent power are displayed, but the meter counts active power.

Click the rectangle in the upper-right corner of the screen to open the settings menu and access the event log. This menu is effectively the main one, since to return you have to select the Status mode; it’s just loaded automatically when you start up.


Sometimes you need to control a load according to a schedule—in other words, you need a simple timer. That’s what the Schedule tab is for.
It’s easy to set up: double-click the desired row, then drag the green area up or down. Double-click the green row afterward to open an additional menu where you can set the time more precisely.

This feature is useful when power to certain rooms (or simply to specific loads) needs to be switched off according to a work schedule. You can set different times for different days of the week.


It’s a little more convenient to do this on a computer, but because the table is oriented vertically, more values fit on screen, yet it still doesn’t fit completely. The red horizontal line shows the current time.


Protection.
Voltage protection: some of the settings are identical to those on the RN-263t. The upper threshold is 240–290 V, and the lower one is 160–230 V. There are also additional options: you can set the shutdown delay for overvoltage to 0.2–2 sec and for undervoltage to 0.2–60 sec.
It’s worth explaining that, like the RN-263t, this unit has three overvoltage trip thresholds and two undervoltage thresholds. However, on the EM-129, the first threshold is adjustable. The modes work as follows:
Gradual increase above the set value; the delay is adjustable
Voltage exceeds the set value by 30 V; shutdown after 0.2 sec
Voltage exceeds 300 V; shutdown after 0.02 sec

For undervoltage, you can set the delay for a gradual drop below the set value. But if the voltage falls to 145 V, shutdown is fixed at 0.25 sec.

Hysteresis is a very useful setting, adjustable from 5–20 V, which can come in handy with a weak power grid.
You can also set the restart delay after a fault (automatic reclosing, or AR). It’s 5 sec by default, and you can specify the number of automatic recovery attempts. Automatic lockout is disabled by default.
The AR time can be set in 0.1 sec increments, which seems excessive to me; 1 sec increments would be enough.


Overcurrent protection is adjustable from 1–63 A, in 0.1–0.2 A increments, with a trip delay of 0.2–10 sec.
There’s also an automatic recovery setting. It’s set to 60 seconds and 3 attempts by default, but you can choose “never,” 1, 2, 3, 5, 7, 10, or “always.” If the device locks out after all attempts have been used, you can reset it by disconnecting the power for a few seconds.

Overpower protection has a few more settings: you can choose between active and apparent power, and you can also disable the function.
This feature is useful, for example, when you agree on a maximum permitted power with a tenant and need to make sure they don’t “forget” about it while advertising a new batch of heaters in their shop.

Frequency protection is a rather unusual setting. I assume it might be useful when powering the device from a generator or converter. The upper threshold is adjustable from 50–65 Hz, the shutdown delay is 5–10 sec, and the AR time is 60 sec by default. You can also choose the number of recovery attempts. Disabled by default.


Log.
While operating, the EM-129 records current, power, and voltage data, saving it to non-volatile memory every five minutes. The archive holds 10,000 records; once full, it overwrites the oldest entries.

Here you can view graphs of power, voltage, current, and energy consumption in kWh. In this case, I had a refrigerator connected, so the power graph looks like a comb, while the energy consumption graph is almost a straight line.


If an event is an alarm condition, it is saved to memory immediately, regardless of the five-minute intervals. You can then click the red dot to see a description of the event.


Connecting to the Overvis cloud service.
Actually, I should have done this from the start, but things worked out chronologically so that I did it later. So before going on to describe the settings, I’ll show you how to connect, although you can change the module settings without doing this.

Either from the main screen or by clicking “Settings,” you can access the list of nearby WiFi networks. Find yours, enter the password, and after saving, the device will try to connect to your network. If everything goes well and the blue LED stays on continuously, you can follow the link provided.


This will take you to the Overvis cloud service. The device’s unique ID will be entered automatically; alternatively, you can use the link or QR code on the sticker.
Enter the password (admin by default) and you’ll see your device—in this case, just one, but you can view several if they’re registered.
To get full access, register by entering your email address, password, phone number, and name. You’ll then receive a registration confirmation by email, and that’s it—the process is complete.


From here, it’s simple: log in with your username and password to get to the menu for selecting connected devices. Since this is cloud access, you’ll also see settings for your account, where you can change your phone number, name, and password.

Selecting a connected device takes you to a screen with the large round button shown at the very beginning of this review. In other words, the interface doesn’t change from here on, and everything described above remains the same.


Device settings.
1. Device name and access password. It’s probably obvious that you should use something more meaningful than EM-129, such as Office, Warehouse, or Store. You should also change the password to something more secure than admin.
You can also set the price per kWh and the currency, since landlords sometimes charge a different rate from what they pay their supplier.
2. Connected network name, password, TCP/IP settings, and assigned IP address (I later used it to connect directly from a computer).
Scheduled vacation—I’m not quite sure what this is for. Selecting it lets you choose a date range using two dates in year/month/day format.
3. Time synchronization settings. I didn’t change anything; it works as is. You can force synchronization with the server or a connected PC.


1. Enable/disable remote access through the cloud service. It’s enabled by default; if you don’t use it, you can turn it off for better security.
2. Front panel lock—or, more precisely, the interval during which the relay won’t respond to the control button. Disabled by default.
Load lock—or, more precisely, disabling automatic recovery for all modes. Disabled by default; maximum duration is 720 minutes.
Reset time for the repeated activation counter: 1–60 min.
Indicator brightness. Probably the most unexpected setting: you can adjust the brightness of the front-panel LED across 15 levels. It actually works :)
3. Reboot the device, clear the log, and do what I mentioned at the very beginning: reset the energy meter. That’s one reason it definitely can’t be used for commercial metering, although there are many more, including the enclosure design and the fact that the device isn’t listed in the state register, etc.


Now for the tests. First, voltage measurement accuracy.
The relay starts up at around 40–41 V. In this case, that means it starts operating and connects to WiFi.


The description specifies an operating range of 100–450 V and a measurement range of 50–450 V.
The first one is actually even better: the relay works from 40 to 450 V. The second, however, is a little worse. It starts measuring at 50 V, as specified, but the last accurate voltage readings are limited to around 388–390 V.
Above an input voltage of 390 V, the readings are too low, and the higher the voltage, the greater the difference. At an input of 450 V, the relay shows just 417 V.
The developer later replied that the actual measurement range is 100–350 V, which is what the paper manual specifies.


Current was a little more complicated. Up to 9 A, I used incandescent bulbs and a couple of different irons. For higher currents, I had to rig up a transformer connected through a Variac, since there was no way I could get 63 A or dissipate 14 kW at home using the usual method.


In principle, you could even call this a pretty good result: the test results are within the specified 2%, and the actual error was just 1%. But, once again, there's a “catch.”
The description specifies:
Current measurement range: 0.3–65 A
Power measurement range: 15–30000 W

I have no complaints at the high end, at least as far as current goes. I saw readings of around 64.5 A; I didn't go any higher because the protection kicked in. But at the low end, things are worse.
I gradually increased the load, starting at 15 W, then 40, 60, and 60+15 W. The relay considered this load below the threshold, even though it exceeded both specified values: 0.3 A and 15 W.
It wasn't very convenient to increase the load gradually beyond that. I don't have an AC load (at least not yet), so I connected a 0.5 A load, which worked fine. In practice, the current at which the relay starts registering it is somewhere between 0.33 A and 0.5 A.


I also ran a couple of additional tests.
First, I measured the voltage drop across the relay contacts at 50 A. The total resistance of the phase busbar came out to about 0.75 mΩ, which is quite good. The power dissipation is just 1.85 W. I think these results also apply to the RN-263t.



The second test checked how well it handled an input voltage of 450 V, the specified maximum.


The relay did, of course, go into protection, but it kept measuring the voltage and plotting a graph—albeit with an offset in the voltage reading. The actual voltage is shown in the photo above. So while I was running the relay through the voltage test, the log filled up with fault messages.


I didn't time it precisely, but it ran for about 50 minutes. The relay was barely warm; the photo shows the top, right side, and bottom.
I measured the temperature of the bottom because that's where the 420 V varistor is, and the input was 450 V. But it didn't even warm up—or at least the thermal camera didn't detect anything unusual.


For the third test, I decided to see what would happen if I connected the relay backwards. Of course, in this case, I'd first have to start it up so the relay would latch (or, more precisely, its equivalent, since it's a polarized relay).
What interested me most was how it would calculate power in this configuration. The test showed that the relay doesn't account for active power at all—or, more precisely, it doesn't even “see” it—but it does fully measure apparent power as it increases.
I think it would be a good idea to log a measurement error in this situation.


Response time.
As I mentioned above, there are three levels for overvoltage and two for undervoltage. I tested two overvoltage settings (medium and fast) and one undervoltage setting (fast). I also tested switching back on after a fault clears.

First, the fault-clear mode, i.e. switching on entirely under the device's control.
1, 2. Switching on after undervoltage
3, 4. Switching on after overvoltage.

My isolation transformer isn't very powerful. I think that's why the sine wave is distorted after it, since the device has a DC-DC converter at its input.
As with the RN-263t, switching on occurs near the peak of the sine wave, specifically on the negative half-cycle.


Response to the voltage dropping below the set threshold.
On the left, the threshold is set to 180 V; the voltage drops to 140 V in the top image and 110 V in the bottom one.
On the right, the threshold is set to 160 V; the voltage rises to 180 V in the top image and drops to 110 V in the bottom one.

In most cases, the relay switched off close to the zero crossing of the sine wave, but not always. It could switch off during either the positive or negative half-cycle. The shutdown delay was 0.25–0.28 sec, which is almost within the specified 0.25 sec.


As last time, I paid more attention to the overvoltage shutdown test, since situations like this are more critical for equipment. The tests will be similar to those for the RN-263t.

First, I set the trip threshold to 240 V and applied 265, 280, 310, and 340 V to the input.
1. 265 V: shutdown after 0.5 sec, as set in the configuration.
2. 280 V: since the difference between the setpoint and input voltage is more than 30 V, it shut down after 0.2 sec, as specified in the instructions.
3, 4. At an input voltage of 290–310 V, the “fast” mode kicks in, so at 310 V shutdown should occur in less than 0.05 sec. In reality, it took 0.02–0.03 sec.
5, 6. At an input voltage of 340 V, the delay was the same: 0.02–0.03 sec.

The shutdown time either matches the specified value or is even shorter, which is better. Shutdown usually occurred at the zero crossing, but sometimes there was a slight delay. I repeated each test several times to check.


The trip threshold was 250 V. In this mode, I tested with input voltages of 265, 310, and 340 V.
1, 2. At 265 V, the delay matched the setting: 0.5 sec.
3, 4. At 310 V, shutdown took 0.02–0.03 sec.
5, 6. At 340 V, the result was the same as in the previous mode.

Everything was just as I described in the previous test: the relay switches off close to the sine wave’s zero crossing, but not every time. Shutdown can occur on either the positive or negative half-cycle.


The shutdown threshold was 280 V. Here I applied 310 V (top) and 340 V (bottom).
Basically, everything is the same as before, but it’s more noticeable that shutdown doesn’t always occur at the zero crossing, although you can see that it is synchronized with the mains to some extent.


During testing, I noticed something odd about the relay’s behavior—more specifically, its AR (automatic restart) mode.
While simulating voltage fluctuations, I also noticed that once the voltage returned to normal, the relay switched the load back on immediately, even though the configured delay was 5 seconds. I contacted the developer, who explained that the AR delay is counted from the moment the relay switches off, not from when the voltage returns to normal. On the one hand, this means the load is reconnected sooner while still observing the delay. On the other hand, the voltage can sometimes go out of range again after returning to normal, resulting in a short on/off cycle, which isn’t very useful.


And a couple of words about the other devices in this series.
Although the EM-129 is a new product, similar devices have actually been around for a while. They offer very similar functionality: they can also work as an electricity meter, a protection device, and a remote load switch, and they can be accessed through the Overvis service. But they differ in design, have a lower maximum current, and cost half as much. The EM-126T relay also has a temperature sensor, but costs a couple of dollars more than the EM-125.
Unlike the EM-129, both devices are aimed at the “consumer” market, so they come with a 3-year warranty. If anyone is interested, I think I could review one of them. Both relays are available through the Russian version of the website.


After testing it, I can say that I’m genuinely impressed with the device—not just because it can measure electricity consumption and switch a load on and off, but mainly because it includes an advanced mains voltage protection system. It really does offer more settings than the RN-263t, while retaining the same basic approach. That’s why I’m planning to replace the relay I installed at home more than 10 years ago.

In many ways, it’s essentially an RN-263t with far more options, both in terms of settings—for example, protection based not only on current but also on power and even frequency—and functionality (Wi-Fi). The power supply circuit has also been completely redesigned, and personally, I think it should be more reliable.

There are, however, a few “caveats” that I think the developers should address.
1. The virtual “button” switches the load on without applying the delay. This could be critical for compressors, for example, if the load is accidentally switched off and back on. I think they should add an option to choose whether to apply the delay.
2. The “button” responds almost instantly, which could lead to accidental shutdowns—especially if the relay controls an entire apartment and the router used to control it is connected through that same relay. You can imagine the result. It would be good to add a press-and-hold delay.
3. The current/power measurement range is specified in the printed (and more accurate) documentation as 0.3 A/300 W. My tests showed that the actual minimum power is closer to 100 W, but that’s still rather high, especially if you’re using the electricity meter function.
4. The varistor is connected to the power circuit without a fuse. The chance of failure isn’t very high—I applied 450 V for an extended period—but even so, for safety, there should be a fuse upstream of the varistor.

That’s all for now. Next, I plan to install it in my home electrical panel, with a few additions that I’ll tell you about another time. I’ll also put it through an additional “test of time,” although it’s been running my refrigerator for almost a week now and has performed excellently, with no false trips or other problems.

I hope this was useful. If you have any questions, I can pass them on to the developers and post their answers.
2800₴ (около $105)
Go to store
This page was found when searching for:
счетчик в розетку с функцией памяти аварийного отключения света, дрл-м 129 к 59, 3, https://www.kirich.blog/obzory/tehnicheskie-obzory/892-wifi-schetchik-elektroenergii-s-funkciey-zaschity-i-upravleniya-em-129-ot-novatek-elektro, 5, реле ем-129, ем-129 аналог, wi-fi счетчик электроэнергии с функцией защиты и управления ем-129, wi-fi счетчик энергии, ем 129 новатек, wifi новатек, регистрация wi fi счётчика em 129, умные счетчики wifi, wi-fi счетчик электроэнергии с функцией защиты и управления, ем 129 от новатек электро отзывы, ekf em 129, ем 129 wi fi счетчик, счётчик электроэнергии wi fi, em 129 счётчик, em129 счетчик электроэнергии, счётчик электроэнергии с wifi, «my.overvis.com», счетчик меркурий 3 5 60 а с «вайфай», overvis.com, em 129 обзор

Questions and answers

Can the EM-129 be used as a commercial electricity meter?

No. The EM-129 is for non-commercial metering and cannot replace a standard meter that can be sealed.

What is the EM-129’s practical minimum measurable power?

Although the paper documentation specifies a lower limit of 300 W, the author’s tests found the actual minimum to be closer to 100 W.

What concerns does the author raise about the EM-129?

The author suggests adding a delay before switching the load on and protection against accidental presses of the virtual button. He also notes that the varistor is connected without a fuse.

The figures from this review are in the measurement database: Other devices


Discounted products


You may be interested in


Discounted products


Support the project

All the content on the site and the advice are free, but we’d be grateful for your support of the project and the channel!

Discuss on the forumHave a question or some experience to share? Discuss the article with the author and readers: the forum is a convenient place to share schematics and photos.
Go to the forum

Only registered readers can comment. It takes a minute to sign up, and you can log in with the same account you use on the forum.

Log inRegister