I’d already been asked about this device, and that’s exactly why I ordered one—to get a hands-on look at it.
This time, I’ll be looking at a power limiter for connected devices. It can help when the combined power draw of the connected loads might exceed the available power limit.


As usual, here’s a link to the Ukrainian version of the site, which will show visitors from Russia an error. For readers in Russia, the link will be different, or you can use this one.

Yes, there are situations where, for example, your home has a 10 kW power limit, but you could accidentally connect a load that exceeds it. The result is that the main circuit breaker trips—and it’s a good thing if it isn’t sealed.
In that case, one option is to disconnect non-priority loads when the total power consumption exceeds the set limit, leaving the essential loads connected.



The review will follow my usual format: inspection, teardown, how it works, a few tests, and, of course, my conclusions.

As usual, I’ll start with the packaging, although there’s nothing unusual here: a branded box with a sticker on the side listing the device model and its basic specifications.


The package contents are as minimal as ever: the device and its manual.


The manual contains all the information needed for connection and setup, as well as the warranty terms. The warranty period is 10 years. As a reminder, if your device breaks, the warranty period is counted from the manufacturing date shown on the device itself, or determined by its serial number, even if you’ve lost the paperwork.
But there’s some confusion here. The electronic version of the manual says:


The product’s warranty period is 36 months from the date of sale.

But the website says:

Warranty: 10 years

I'll need to check, but in any case the paper version takes priority.


Technical specifications from the manual.


Externally, it's also a standard module.


1. The case is 52 mm wide, i.e. three modules, as stated in the manual. For some reason, though, the manual gives the width as 35 mm, which corresponds to two modules.
2. On the back are a latch and a serial number sticker.
3. At the top is a four-terminal block for connecting to the mains. Only the outer terminals are used.
4. The same type of terminal block is at the bottom, with the contacts of the internal relay brought out to it.

You can also see that the relay has two holes, one at the top and one at the bottom, for routing the wire whose current is to be measured.


The front panel has a three-digit, seven-segment LED display, operating mode switches, LED indicators for relay activation and overload, and potentiometers for setting the on/off delay and trip power threshold.
The operating mode switch lets you select the power setting multiplier and load type (active or apparent).


The dimensions and functions of the controls and indicators, from the manual.


The relay is very easy to take apart: remove the four self-tapping screws and lift off the top half of the case.


Clever construction has become something of a trademark of Novatek, and this device is no exception. It consists of four boards, three of which form a U-shaped assembly and connect to the main board via connectors.


1. The top board holds the display and trimmer resistors. The designers were clearly short on space, so two of the trimmers are on the underside and one is on top. Overall, it's a neat and simple solution.
2. The underside of this board has a few small components and the remaining two trimmer resistors.
3. One of the side boards carries an ATmega8A microcontroller and an op-amp.
4. There are no other electronic components on the boards; the third one is just an adapter board.


I remove three more screws and take the main board out of the case.


Overall, the assembly is reasonably neat, though some areas could be a little tidier.
You can see the current transformer, as well as the power supply, which uses a capacitive dropper and Zener diodes—a very common design in devices like this.
The relay is rated for load currents up to 10 A, naturally for a resistive load. The manual, however, specifies a current of only up to 8 A, and the manufacturer's website gives 7 A.
The current transformer’s burden resistor is visible next to the relay.


The underside is also generally fine, except for the very small clearance between the trace from the relay contacts and the diode connected across the coil. Of course, if the relay is switching the same mains supply, this isn't a major concern. But the relay could also switch other circuits, so I'd increase the clearance between the diode and relay contact traces a little.


Two relay connection options are provided.
A. The relay controls an additional contactor; the output current is limited by the contactor's rating.
B. The internal relay switches the power circuit directly; current is limited to 8 A for a resistive load.

I should remember to mention the typo in the schematic.


When powered on, the display shows the measured power—in this case, 0, since the relay is switched on by itself. Power consumption is 1–1.2 W with the relay on and all three digits lit.


1, 2. Off-delay adjustment. At low settings, you can set any time you like; at higher settings, the increments are 5 seconds. I could only get the maximum of 300 seconds by pressing the screwdriver all the way in; when I let go, it switches to 295.
3, 4. On-delay adjustment. The same applies here, except that you can also select infinity, so the relay won't switch back on by itself after being turned off.


Adjusting the power threshold at which the load will be switched off.
The 10/1 switch changes the multiplier: in the first position, the adjustment is in 200 W increments; in the second, in 20 W increments. Sometimes, though, it can jump from, say, 1.4 kW straight to 1.8 kW, skipping 1.6 kW.


1. The device starts up at around 130 V, lights the indicator, and displays a low-voltage warning
2. At 165 V, it switches to normal operation and, if there is no overcurrent, turns on the relay.
3. It tripped on overvoltage protection at 258 V.
4. As the voltage drops, it returns to normal operation at 252 V. The hysteresis is 5 V, as specified, but the thresholds are slightly lower: 253/258 instead of 255/260.

The relay has two shutdown delay modes. The slow mode applies when the voltage goes outside the 160 or 260 V limits: the delay is 5 sec in the first case, and 1 sec to switch off and 5 sec to switch back on in the second.
If the voltage drops below 130 V or rises above 300 V, the relay switches off within 0.05 sec.


Testing shutdown when the voltage goes beyond the extreme limits.
1, 2. When the voltage drops below 130 V, although in my case it actually only switched off when the voltage fell below 120–122 V.
3, 4. A sharp rise in voltage above 300–310 V.

As you can see from the waveforms, shutdown occurs after about 3–5 half-cycles, or 0.03–0.05 sec. The specified time is 0.05 sec, so everything is fine here too.



For the next tests, I connect a socket through the relay. This is where I discovered that the input terminals are wired in parallel, i.e. 1+2 and 3+4. I think they'll fix this soon, since with this wiring it's easy to burn out both the terminals themselves and the traces on the circuit board.
But this setup turned out to be convenient for my test.

I also noticed a design flaw: one of the wires has to pass through the relay housing, and the only guide inside is the current transformer. This reminded me of my old review, where I took apart a Chinese power meter and showed a much better solution to this problem. I think the photo makes the idea clear.


I'll test how closely the displayed power matches the actual power using a much-simplified setup, since I don't have a reference wattmeter, and judging by current alone isn't entirely accurate.
All I can say is that at a current multiplier of 1, the device definitely "sees" a load above 15–16 W (a small incandescent lamp); the wattmeter at the input reads 17 W.
After that, I tested it at around 139 W (an incandescent lamp), 400 W, and 2000 W (ordinary irons).

Yes, it's a resistive load, but it's what I have. The photo shows that the OM-110 underreads. The actual difference is a little smaller, since I know for sure that my wattmeter reads about 2–3% high; I usually take that into account in my calculations.


As another test, I checked the measurement with a switching power supply as the load. The error is in the same direction as with the resistive load, but noticeably larger. Even allowing for a 3% error in my wattmeter, the OM-110's error is around 3.5–4%. With the resistive load, the error was closer to 2–2.5%, against the specified 2.5%.


To assess how it handles an inductive load, I connected a basic variable autotransformer. I don't have any powerful inductive loads at home that are convenient to use.
In resistive-load measurement mode, the device showed 0.01 kW, while the wattmeter read 16 W.
In apparent-power measurement mode, the device displayed 0.02 kVA, occasionally jumping to 0.03 kVA. The wattmeter doesn't have this display mode, but the current in the circuit was about 0.12 A.


Measurements are certainly useful, but since this device isn't really a measuring instrument, I think it's more important to show how it behaves with different wiring configurations.

First, I assembled the circuit as shown in the instructions: mains, a power-limiting relay, and a load. The relay measures the current in the load circuit and disconnects it if the power exceeds the limit.
On the left is how I wired it; on the right is the correct way, with the relay switching the live wire. The two circuits work the same way.


As expected, I got a "blinker": with low settings for the relay's off and on delays, it periodically switches the load off and on if the current in its circuit is above the set threshold.
This behavior is normal, but I find it very inconvenient. The sensible options are to increase the time intervals to the maximum, or turn the on-time adjustment all the way to the right; then the load won't switch back on by itself.


One possible solution is to split the loads into two groups: priority and non-priority. In this case, the secondary load will be switched off if the power on the priority load line exceeds the set limit, thereby reducing the total power.


A 130 W incandescent bulb was connected, with a 15 W bulb as the non-priority load. The maximum power was set to about 100 W.

The video might make the timing seem illogical, but everything is actually working as it should: the display alternates between showing the time until switching on or off and the power in the load circuit.


Or here's the same setup as before, but this time I set a higher threshold and connected a more powerful load in addition to the one already connected.


This makes for a more realistic demonstration. We have a secondary load that can be switched off, a primary load already connected that doesn't cause an overload when combined with the secondary load, and an overload simulation.

So, in principle, everything works correctly. But when setting it up, you need to do at least a simple calculation to figure out how much you can reduce the power by switching off the secondary load without causing an overload even after it is switched off.
Of course, you could also monitor the current in its circuit, but then you might run into the problem shown in the first diagram.


Just as an experiment, I decided to see how the device behaves as the load is gradually increased and decreased. I set the power threshold to 0.06 kW, connected a load through a variac, and started increasing the power.
At 0.07 kW, the OM-110 tripped and began alternating between displaying the load power and an error message.
After I reduced the load power, the OM-110 returned to normal operation and switched on the relay.


It would all be great if it weren't for one thing: the device has no hysteresis. In other words, it reacts even to a one-digit change in the least significant place, disconnecting the load when the display reads 0.07 kW and reconnecting it at 0.06. As a result, it's quite easy to get it into a state where even the slightest fluctuation in load power makes it go haywire.
Of course, I made the effect worse here by setting the delays to zero, but I think at least a little hysteresis would have helped.


Conclusions.
Subjectively, the device works fine. It reads power a little low, but it's hard to say for sure without an accurate wattmeter. There are a few minor discrepancies: for example, the fast cutoff happens at 120 V rather than the specified 130 V. Overall, though, it performs the advertised functions.

A few minor design suggestions:
1. It would be good to add a plastic tube so you don't have to poke the wire in blindly and risk hitting one of the components.
2. The adjustment circuit could use a little tweaking. As I mentioned, I couldn't set the specified 300-second switch-off delay—or rather, I couldn't get it to stay set.
3. Increase the spacing between the PCB traces around the relay output and the diode connected in parallel with its coil.

It could also use hysteresis for the power cutoff.

Now, about the relay itself and what it can do.
It's basically just a power threshold relay that trips when the power exceeds a set limit. The only additions are an adjustable cutoff threshold, adjustable on/off delays, and the option to select either a multiplier for the adjustment or total or active power.
So this relay doesn't have any special capabilities. Its job is simply to switch a circuit off or on when the power goes outside the set limit.

It's worth noting, though, that the manufacturer added a useful feature of its own: a voltage relay. It's genuinely handy, but in some situations it can work against the user because there are no voltage threshold adjustments. I would probably add a small button that lets you adjust the trip voltage while held down, then saves the setting when released.

Personally, I think the right way to manage loads with a power limit is to take a comprehensive approach. For example, you could have a module that not only monitors several circuits but also takes the power of the connected loads into account and switches off only those that would actually overload the mains. Ideally, the device would remember the power of connected loads and take it into account when reconnecting them. But those are just ideas that came to me while testing the device.

After writing the review, I realized that this relay is similar to the RN-263t. However, the RN-263 switches off when the current limit is exceeded, while the device reviewed here trips on excess power. In my opinion, current is the more appropriate parameter to use for cutoff.
The reason is that current is the key parameter. For example, at 240 V and 10 A, the power is 2.4 kW. But at 180 V, the current at the same 2.4 kW will be 13 A, which could overload the mains even though the relay thinks everything is fine.

The device is available in many versions with different features.
1. RMT-101 — a maximum-current relay. This is exactly what I meant above: like the OM-110, it measures current up to 100 A, but trips on excess current rather than excess power. At the same time, the RMT-101 does not have a “voltage relay” function.
2. OM-163 has more functions, but measures current only up to 63 A; on the other hand, it has a built-in relay rated for up to 63 A.
3. ОМ-121 also measures current up to 63 A, like the OM-163, but all control and monitoring are handled via RS485, and its internal relay is rated for only 1 (5) A.
4. РМТ-104 is an overcurrent relay with a measurement limit of 400 A.
5. And ОМ-310 is a three-phase version. It works with both internal CTs (up to 30 kW) and external CTs (up to 450 kW), and can control two loads.


That’s all for now. I hope this was useful, and as always, I’ll be glad to hear your questions and comments.
930₴ (около $34.5)
Go to store
This page was found when searching for:
1, https://www.kirich.blog/obzory/drugie-obzory/1046-rele-ogranicheniya-moschnosti-om-110-ot-novatek-elektro, ом-110 ограничитель мощности, реле ограничения мощности с алиэкспресс отзывы обзор

Questions and answers

What does the Novatek-Electro OM-110 power limiter do?

It disconnects non-priority loads when their combined power exceeds the set threshold, helping prevent the supply from being overloaded.

At what voltage does the OM-110 trip on overvoltage?

In the test, it entered protection at 258 V and returned to normal operation as the voltage fell to 252 V.

What switching current is specified for the OM-110?

The manual specifies a limit of 8 A for an active load, while the manufacturer’s website gives 7 A. The author notes that the internal relay is rated for up to 10 A.


Discounted products


You may be interested in


Discounted products


Support the project

All the content on the site and the advice are free, but we’d be grateful for your support of the project and the channel!

Discuss on the forumHave a question or some experience to share? Discuss the article with the author and readers: the forum is a convenient place to share schematics and photos.
Go to the forum

Only registered readers can comment. It takes a minute to sign up, and you can log in with the same account you use on the forum.

Log inRegister